EVAPORATOR APPROACH
Evaporator Approach is the difference between the saturated
temperature of the suction pressure and the leaving chilled water
temperature.
Normally, in a high efficiency chiller with a flooded type
evaporator, the evaporator approach should be less than 2 degrees C.
(3.6 degrees F.).
When historical information on a unit is available, it is always
a good idea to compare historical evaporator approach readings with
the current reading.
High evaporator approach results in a loss of efficiency and
capacity in the chiller.
Potential Causes of High Evaporator Approach:
Loss of refrigerant charge in air cooled chiller – if the
chiller experiences high inverter temperature alarms or faults and
the evaporator approach is higher than normal, there is an excellent
chance the chiller has lost charge. In this case, the actual
liquid level in the evaporator will be less than the liquid level
setpoint.
On a water cooled condenser chiller, condenser level is being
controlled to a setpoint. Loss of refrigerant charge will
result in lower liquid level in the evaporator. Verify visually
the liquid level in the evaporator. If liquid level not
visible, try lowering the condenser liquid level setpoint, which
should raise the liquid level in the evaporator...... This also
should result in some reduction of evaporator approach. Caution
must be taken to not lower the condenser liquid level setpoint to the
point where there is a loss of liquid ¨seal¨ on the compressor
cooling connection. This will result in bubbles in the motor
cooling line sightglass and increasing compressor inverter
temperatures.
Fouling of the waterside of the evaporator tubes – This is not
very likely that the evaporator tube watersides have fouling, but
this is Always a possibility that must be considered.
Problem with the compressor suction pressure/temperature sensor –
A small ¨drift¨ in the suction pressure sensor reading can
dramatically affect the performance of the chiller. This can
easily be verified by connecting a pressure manifold to the system
and verifying the suction sensor pressure reading. I have actually seen this problem on several different installations.
Problem with the leaving chilled water temperature sensor – This
can be verified by measuring chilled water temperature with a meter.
If no meter available, turn of chiller and verify that entering and
leaving chilled water readings are the same.
No comments:
Post a Comment