Tuesday, October 1, 2019

CONDENSER APPROACH

CONDENSER APPROACH

On a chiller with water cooled condensing, this is the difference between the saturated temperature of the discharge pressure and the leaving condenser water temperature.  On a high efficiency chiller with flooded type condenser, this should normally be no more than 1 to 2 degrees C (1.8 to 3.6 degrees F).  Where historical information is available, it is always good to compare previous approach readings with the current Reading.

High condenser approach will cause loss of chiller efficiency and capacity.

The most likely case of increasing condenser approach is fouling of the waterside of the condensing tubes.  Looking at the quality of the condenser water itself can give an indication of the probability of condenser tube waterside fouling.

High condenser approach may also be due to ¨drift¨ in the pressure reading of the compressor discharge pressure/ temperature sensor or the reading of the  leaving condenser water temperature sensor.  These items can be verified by comparing against a refrigerant manifold reading or temperature meter reading, as appropriate.

On a chiller with air cooled condenser, the approach is the difference between the saturated temperature of the discharge pressure and the ambient air temperature.  Normally, this will be 10 to 15 degrees C.

Possible causes of high approach on air cooled chillers can be error in the compressor discharge pressure sensor Reading.  A likely cause is dirty coils.  This can easily be discerned with a visual inspection.

No comments:

Post a Comment