PREVENTING
SURGE:
Surge
typically occurs when the compressor is operating with a high
pressure ratio (PR), or when either the suction or discharge pressure
change more rapidly than the compressor controls can adjust the
compressor speed (RPM´s) and/ or inlet guide vane (IGV) position.
Pressure
Ratio (PR) is a number that is calculated based on the relationship
between the discharge pressure and the suction pressure. Pressure
Ratio for water cooled chillers typically will be on the order of 2.0
to 2.5. Due to the higher discharge pressure experienced by Air
Cooled units, Pressure Ratio for Air cooled chillers will typically
be on the order of 2.5 to 3.0. Higher condenser water temperature or
higher ambient temperatures will result in higher Pressure Ratio.
It
is important to recognize that the compressor is experiencing surge
and take action to prevent this from occurring. This action may be
the repair of a defective component of the chiller or an adjustment
to the chiller control loop algorithm parameters.
Routine
review of the chiller controller logs and the compressor histories is
important to assist in recognizing that the compressor is entering
surge.
Anytime
there is a Front Radial Bearing Displacement Fault, the cause must be
investigated. Particularly if this Fault is displayed repeatedly.
As
an overall rule, the compressor should not cycle more than three to
four times per hour under normal operating conditions.
There
are many possible causes of surge, however, following are some of the
more common ones encountered:
Chilled
Water Flow Switch inoperable in the closed position or jumped out
– This condition is particularly dangerous for the compressor. If
the compressor starts with no chilled water flow or the chilled water
flow is reduced/ eliminated during compressor operation, the suction
pressure will rapidly drop. The compressor controls can´t adjust
rapidly enough to prevent the compressor entering into a surge
condition. Eventually, the compressor shaft displacement will exceed
the safety limits of the controls due to the surge and the compressor
will shut down, typically with a Front Radial Bearing Displacement
fault.
The
continued operation of the chiller under this condition, with
repeated Front Radial Bearing Displacement faults has a high
probability of eventually resulting in damage to the touchdown
bearing.
Lack
of Water Flow proof or inoperative flow proof on condenser of water
cooled unit – If there is no water flow proof installed to
protect the chiller against operating with low water flow, a
condenser pump becoming inoperative will force the compressor into a
surge condition.
High
Ambient Conditions in combination with lower chilled water setpoint
– In cases where the client is operating the chiller at low load
with a chilled water setpoint below 4.5 degrees C (40 degrees F.),
during high ambient conditions, it is imperative that proper
adjustments be made to the chiller control parameters to prevent the
compressor entering in surge.
Under
these conditions, the compressor will likely be operating close to
the surge rpm limit. As the the chiller controls attempt to reduce
compressor capacity to meet the low load at the same time maintaining
enough compressor rpm to overcome the difference in suction and
discharge pressures, surge is a risk.
High
Evaporator Approach – High evaporator approach (more than 8
degrees C or 14.4 degrees F.) will result in a lower than normal
suction pressure. This, in combination with higher ambient
conditions can also result in the compressor operating close to and
occassionally entering into surge condition.
Failure
of Inverter Temperature Sensor or Motor Cavity Sensor – If
either of these sensors fails such that it is giving a higher than
normal reading, the compressor controls will automatically reduce
compressor rpm in order to limit the amount of heat being generated
by the inverter or the compressor motor itself and forcing the
chiller into a surge condition.
Chiller
Operation with rapidly changing load – In cases where the
chilled water loop is extremely small or the load on the chilled
water loop suddenly drops off, the compressor will tend to cycle
frequently and has risk of entering surge as the load disappears and
the compressor attempts to reduce compressor capacity in response to
the changing load.
In
this case, the compressor may enter surge before the chiller control
algorithm reaches the point where the compressor will be cycled off.
Repeatedly cycling the compressor under these conditions can result
in surge and compressor damage.
Failure
of the Compressor Suction Pressure Sensor – The compressor is
equipped with a pressure/ temperature sensor on the compressor
suction and discharge. If the suction pressure sensor begins to read
high, the compressor controls can drive the compressor into surge
repeatedly due to the fact that the compressor does not really know
where it is operating on it internal compressor map.
It
is important to routinely verify the suction pressure sensor accuracy.
There is no calibration possible on this sensor. Sensors reading
improperly must be replaced.
No comments:
Post a Comment